Calculation – Secltion Procedure.
Determine volume of space to be ventilated
Volume (ft3) + L x W x H, where L + Length, W = width, H=Ht. of building
Select Air changes par hour inside working area from Table A
Calculate required ventilator rate Q (cfm)
Q (cfm)=(Volume (ft3) X Air change )/60
Determine number of ventilators=(ventilation Rate Q)/(Exhaust capacity)
EXAMPLE:
Building dimensions with L = 100ft, W=60ft, H=20ft,
Volume (ft3) =120000 ft3.
Air change rate selected = 12 times per hour. (From table - A)
Calculation required ventilation rate Q (cfm)
Q (cfm)=(Volume (ft3) X Air change )/60
Ventilators rate Q (cfm)=(120000 X 12)/60=24000 CFM
Refer table B , select suitable model from table is AV - 500
Exhaust capacity = 1084, 1 ventilator par hour.
Under wind velocity of 5 mph , temp. diff. of 5 degrees, stack height = 20 ft
Air ventilator require Quantity =24000/1084=22 Nos
Selection is 22 nos. of AV -500